Iniciar sesión:
Votos - 3, Puntuación media: 3.7 ( )

Manual de usuario Empire Comfort Systems, modelo DVP42FP7(0,1,2,3)(N,P)-1

Fabricar: Empire Comfort Systems
Tamaño del archivo: 3.44 mb
Nombre del archivo: 54cb9fad-469d-4b5a-859e-6696d379311b.pdf
Idioma del manual:en
Enlace gratuito para este manual disponible en la parte inferior de la página



Resumen del manual


Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition. Checking Manifold Pressures Both Propane and Natural gas valves have a built-in pressure regulator in the gas valve. Natural gas models will have a manifold pressure of approximately 3.5" w.c. (.871kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484kPa). Propane gas models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) at the valve outlet with the inlet pressure to the valve from a minimum of 10.8" w.c. (2.68kPa) for the purpose of input adjustment to a maximum of 14.0" w.c. (3.484kPa). *NOTE: Remote "RF" Models - 10.5" w.c. maximum Figure 7 17375-10-0706 Page 9 Page 10 17375-10-0706 REAR VENT CONVERSION Note: Discard insulation & retainer when using vertical venting off VERTICAL VENTING HORIZONTAL VENTING FLUE INSULATION INSULATION RETAINER INLET VENT COLLAR INLET VENT COLLAR FLUE OUTLET COLLAR FLUE COVER PLATE (See note above) INLET VENT COVER PLATE FLUE COVER PLATE INLET VENT COVER PLATE Note: It is recommended that the flue cover plate tab be pulled outward prior to removal. This will ensure that the plate is not accidentally dropped inside the rear air chamber. Note: Discard insulation & retainer when venting off top of fireplace. Converting flue take-off to rear venting When switching out the flue and inlet vent collars to run horizontally off the rear vent, the following steps must be taken. 1. Remove the inlet vent collar (8 screws) and flue collar (4 screws) from the top of the fireplace, and set to the side. 2. Remove the inlet cover plate and flue cover plate located on the back of the fireplace. These will be used to close the top flue and inlet openings. 3. Insert the insulation retainer bracket and insulation into the top flue pipe before reinstalling the flue cover plate over the top flue with 4 screws. 4. Reinstall the inlet cover plate over the top inlet opening with 4 screws. See illustration above.. 5. Install the flue collar assembly to the rear flue with 4 screws. 6. Install the inlet vent collar to the rear of the fireplace with 8 screws. 7. This completes the conversion for a rear vent application. Note: for top vented installations, the insulation and retainer are to be removed from the flue pipe and discarded. VENT SYSTEMS The following vent systems are acceptable for use with the DVP (42,48) series fireplaces: Simpson Duravent® GS 5" - 8", Refer to Page 23 *American Metal Products 5" - 8" *Selkirk Direct-Temp® 5" - 8" *Security Secure Vent® 5" - 8" Empire Flexvent Kit DVVK-5F, Refer to Page 26 * Can not be used in side wall horizontal vent installations in the State of Massachusetts. INSTALLATION Framing and Finishing 1. Choose unit location. 2. Frameinfireplacewithaheaderacrossthetop.Itisimportantto allow for finished face when setting the depth of the frame. 3. Attach fireplace to frame using adjustable frame. Preset depth to suit facing material (adjustable to 1/2", 5/8" or 3/4" depths). 4. Use (8) 1/2" hex-head screws supplied in hardware package, to screw through slotted holes in drywall strip and then screw into pre-drilled holes on fireplace side. Measure from face of fireplace to face of drywall strip to determine final depth. Vent Pipe Clearance Note: Maintain one inch (1") of clearance around vertical vent Figure 8 pipe. See Fig. 9A. For horizontal vent, maintain a minimum 1" clearance to the bottom and sides of the vent, and 3" clearance to combustibles above the vent pipe. See Fig. 9B VENT PIPE Top of Vent 1" MINIMUM CLEARANCE AROUND VENT PIPE Combustibles NOT allowed in shaded Figure 9A area 3"(76 mm) 5” Diameter flue 8” Diameter intake vent 1"(25 mm) 1" (25 mm) Figure 9B 17375-10-0706 Page 11 INSTALLATION (continued) Flush Mount Mantel Installation (Figure 10) The fireplace must extend 3/4" beyond finished wall surface when using a flush mount mantel. Refer to Figure 10 to locate nailing flanges on fireplace sides. Mark and drill two (2) 1/8" holes into fireplace side to mount each nailing flange. Use eight (8) 1/2" hex-head screws supplied in hardware package to attach nailing flanges to fireplace sides. Figure 10 Framing (Figure 11) Fireplace framing can be built before or after the fireplace is set in place. Framing should be positioned to accommodate wall covering and fireplace facing material. The fireplace framing should be constructed of 2 x 4 lumber or heavier. The framing headers may rest on the fireplace standoffs. Refer to Figure 11 for minimum framing dimensions. CAUTION: MEASURE FIREPLACE DIMENSIONS AND VERIFY FRAMING METHODS, AND WALL COVERING DETAILS BEFORE FRAMING CONSTRUCTION BEGINS. Framing dimension "A" includes a three inch clearance for standoffs on firebox. After installing firebox into framing, the finished wall surface must cover the three inch...

Otros modelos de este manual:
chimeneas - DVP42FP3(0,1,2,3)(N,P)-1 (3.44 mb)
chimeneas - DVP42FP9(1,3)(N,P)-1 (3.44 mb)
chimeneas - DVP48FP3(0,1,2,3)(N,P)-1 (3.44 mb)
chimeneas - DVP48FP7(0,1,2,3)(N,P)-1 (3.44 mb)

Comentarios



Tu reseña
Tu nombre:
Introduzca dos números de la imagen:
capcha





Categoría