• When the water collects to level (A) in the pump reservoir, the drain pump begins to operate and discharges the water. • When the water level drops below level (B), the drain A B pump will stop. NOTE: • If for any reason the water level exceeds that of level (A) in the pump reservoir, an overflow Drain Switch will stop the compressor operation. • If the Fan Mode Control DIP Switch (see pg.13) has been set from the COOL to the STOP position, the Fan will also turn off while the drain pump is discharging water. 15 HOSE INSTALLATION Note: The OP60 is equipped with a 20 foot (6 m) hose. Connect the 20 foot (6 m) hose to the drain outlet spout and feed it through the grommet on the right hand side of the unit. Note: Do not use more than 18 feet (5.5 m) of drain hose vertically. This is the maximum head (lift) of the Condensate Pump. When securing the drain hose to the highest vertical position (no more than 18 feet (5.5m)) and running the hose to the drain, run the drain hose on a downward slope at a rate minimum of 1/4 inch (6.25 mm) per foot for proper drainage. DRAIN HOSE DRAIN STEM DRAIN HOLE DRAIN HOSE 1/4" (6.25 mm) TAPER PER FOOT CONDENSATE PUMP GROMMET 18' (5.5 m) MAX 16 DAILY INSPECTION & MAINTENANCE Emptying the Drain Tank To empty the drain tank, refer to instructions, page 14. Cleaning the Air Filters Clean the air filters once a week. If the unit is used in a dusty environment, more frequent cleaning may be required. A dirty air filter reduces air output resulting in a decrease of the cooling capacity. Filter Removal Method . Turn the unit off, by pressing the COOL ON/OFF button. If a program is running, you must first press the Program RUN button. . Remove the 2 air filters. NOTE: To remove the filters from the Office Pro 60, open the front panel and side panel filter doors. On the side panel door, carefully remove the filter element from the VELCRO. attachment points. On the front, unclip the wire frame and remove filter. CLIP WIRE FRAME VELCRO. ATTACHMENTS 17 CLIP FILTER FILTER DAILY INSPECTION & MAINTENANCE (cont.) Cleaning Method . Remove dust from the element with a vacuum cleaner, or rinse in cold or lukewarm water. If the element is extremely dirty, wash with a neutral detergent. . After the element has been cleaned, rinse with clean running water, allow to dry, then FILTER reinstall. In-Season/Off-Season Inspection & Maintenance ¦ In-Season . Check the prongs and surface of the power cord plug for dust and/or dirt. If dust and/or dirt are present, wipe off with a clean, dry cloth. . Check the power cord, plug and prongs for damage or excess play. If any damage or excess play is found, contact your MovinCool reseller for repair. . Check the air filters and drain tank. . Clean the outside of the unit(s) with a damp cloth or mild nonabrasive cleaner. ¦ Off-Season . Operate the unit in Fan Only mode for 8 hours. Note: Operation is necessary to dry out the inside of the unit. . Disconnect the power cord from the AC outlet. . Check the prongs and surface of the power cord plug for dust and/or dirt. If dust and/or dirt are present, wipe off with a clean, dry cloth. . Check the power cord, plug and prongs for damage or excess play. If any damage or excess play is found, contact your MovinCool reseller for repair. . Clean the air filters. . Empty all water from the drain tank. 18 TROUBLESHOOTING Office Pro 60 Self-Diagnostic Codes Self-Diagnostic Codes will be displayed on the Control Board under the following conditions: dF When the evaporator freezestat disengages the compressor. FL When the drain tank switch shuts off the unit (FULL TANK LED flashes). AS When unit disengages the compressor while the condensate pump is discharging water. HP When the high pressure switch disengages the compressor. LO Lowest temperature set point. TANK FULL SET POINT F C ROOM TEMP AM PM SET TEMP CLOCK/TIMER FAN ON/OFF COOL ON/OFF PROGRAM Office Pro 60 SET START TIME END TIME SET CLOCK RUN HRS MIN Check the following points before calling a qualified technician. SYMPTOM POSSIBLE CAUSE REMEDY Unit does not operate . Ground fault breaker tripped . Drain tank is full (FULL TANK LED will be flashing) Reset breaker Empty the drain tank Insufficient cooling . Dirty/blocked air filters . Air inlet/outlet blocked . Improper temperature setting Clean air filters Clear air inlet/outlet Set to desired position If symptoms persist after the above actions have been taken, turn the unit off, disconnect the power cord plug and contact your MovinCool reseller. 19 TECHNICAL SPECIFICATIONS ITEM/FEATURES OFFICE PRO 60 Rating Conditions dry bulb 95. F (35. C) wet bulb 83. F (28.2. C) humidity 60% Specifications power frequency 60Hz line voltage single phase 208/230V power consumption 7.1 Kw current consumption 33 Amps power factor 99% starting current 140A power wiring 6 (3-core) AWG Cooling Unit cooling capability cooling system 15,100 Kcal/hr 60,000 BTU/hr direct expansion Blower type of fan air volume: evaporator (high speed) evapo...