Iniciar sesión:
Votos - 2, Puntuación media: 3.5 ( )

Manual de usuario Follett, modelo HCE1000W 50Hz

Fabricar: Follett
Tamaño del archivo: 3.32 mb
Nombre del archivo: 82cce3b8-fe38-4097-a9d7-531b0a4e5ca9.pdf
Idioma del manual:en
Enlace gratuito para este manual disponible en la parte inferior de la página



Resumen del manual


Even if pressure fall-back below the reset point of 295 psi, the error will not clear and the machine will not restart. Note: Split Systems do not have a High pressure sensor on the evaporator module. DRAIN CLOG: The drain clog sensor, located in the plastic drain pan behind the drain solenoid, will detect the presence of water just below the top edge of the pan. If water does not properly flow out of the drain pan it will rise to the sensor, especially during a self-flushing purge cycle. LO WATER: 1. There is a sensor in the water reservoir that reaches down to the very bottom. The machine will not start if water is not present at this sensor. 2. A hard error will occur should water not be present within 60 seconds of power up or if the sensors are disconnected or damaged. Relay output indication: Each relay on the board has an indicator light associated with its output. For example, when the relay for the water feed solenoid is energized, the adjacent indicator light glows green. Comp/Sol output: The output for the compressor is labeled COMP/SOL. For split systems, where the condensing unit is mounted remotely from the evaporator module, the COMP/SOL output is wired to the refrigerant solenoid. 15 Wiring diagram #15 4 801 CHURCH LANEEASTON, PA 18040, USA800-523-9361 OR 610-252-7301FOR SERVICE CALL: ON THE WEB: JUMPER 16 Compressor data Compressor current draw Air-cooled Ambient air temp. 60°F/16°C 6.4A Water-cooled Condenser water temp 50°F/10°C 70°F/21°C 6.4A 60°F/16°C 80°F/27°C 6.8A 70°F/21°C 90°F/32°C 7.4A 80°F/27°C 100°F/38°C 7.6A 90°F/32°C 6.5A 6.6A 6.8A 7.3A 7.5A Locked rotor amps 54 Gearmotor data Brother Gearmotor current 2.8A (nominal) Locked rotor amps 15 amps Resistance of windings 208-230 vac gearmotor (Brother) 6.2. Compressor start winding 3.0. Compressor run winding 1.4. Fan motor 38. 17 18 Mechanical system Evaporator disassembly 1. Press PURGE button to purge evaporator, and then turn power OFF. 2. Unscrew and remove stream divider as shown. 3. Unplug and remove gearmotor as shown. 4. Remove all traces of anti-seize compound from the auger shaft. Fig. 13 Fig. 14 Fig. 15 5. Unscrew and disconnect transport tube from louvered docking assembly. 6. Unplug sensor at the electrical box. 7. Remove vent tube from shuttle housing as shown. 19 Fig. 16 8. Loosen nut on V-band clamp and remove. 9. Remove V-band clamp from front of evaporator. 10. Remove main housing as shown. Fig. 17 11. Remove and discard mating ring and seal. 12. Carefully remove auger. 20 Lube with soap touch Do not Cardboard disc Fig. 19 3. Press new mating ring into main housing as shown. 4. Lube the shaft with liquid soap in the area shown and slip on seal and spring. Note: Do not touch the sealing surfaces. Use cardboard disk to install. Fig. 20 5. Reinstall main housing as shown. Evaporator reassembly Fig. 18 1. Remove and inspect O ring seal. Discard if damaged in any way. 2. Clean O ring groove. Lubricate O ring and reinstall. 21 Fig. 22 11. Reconnect transport tube to louvered docking assembly. 12. Plug sensor in at the electrical box. 13. Reconnect vent tube to the shuttle housing as shown. Apply petrol-gel Fig. 23 14. Apply a light coat of anti-seize compound to the auger shaft. 15. Install gearmotor, making sure that insulation is properly seated between gearmotor and main housing as shown. 16. Firmly tighten four gearmotor bolts in place. removed for clarity Note: Shuttle housing Fig. 21 6. Orient auger shaft with keyway in the upward position. 7. Force main housing into position against evaporator and place 1/4" (7mm) diameter Phillips screwdriver into hole in the auger shaft. 8. Replace V-band clamp as shown. 9. Replace nut on V-band clamp and tighten. 10. Remove screwdriver. 22 Fig. 25 20. Remove bolt and reinstall the washer and bolt. Place retainer over bolt and secure with nut and washer. Apply petrol-gel Fig. 26 21. Lubricate body of stream diverter with petrol-gel and reinstall. 22. Plug gearmotor power cord into electrical box. Fig. 24 17. Insert a bolt into the auger shaft and finger tighten. 18. Using a wrench, rotate the shaft clockwise to align the keyways in the gear housing and the shaft so as to accept the key. 19. Insert the key into the keyway. 23 thermostatic expansion valve compressor High pressure vapor High pressure liquid Low pressure liquid Low pressure vapor Low side slrvice port high side service port condenser filter dryer high side refrigeration line run low side refrigeration line run Refrigeration system diagram Air temperature Air-cooled condensers 60°F/16°C 70°F/21°C 80°F/27°C 90°F/32°C 100°F/38°C Pressure (psig) discharge/suction 217/29psi 250/32psi 284/35psi 325/39psi 366/43psi 1497/200kPa 1724/221kPa 1959/241Kpa 2241/269kPa 2524/296kPa 14.96/2.00bar 17.24/2.21bar 19.58/2.41bar 22.41/2.69bar 25.23/2.96bar Water temperature Water-cooled condensers 60°F/16°C 70°F/21°C 80°F/27°C 90°F/32°C 100°F/38°C Pressure (psig) discharge/suction 275/34 275/34 275/34 280/34 302/36 18...


Comentarios



Tu reseña
Tu nombre:
Introduzca dos números de la imagen:
capcha





Categoría