Iniciar sesión:
Votos - 1, Puntuación media: 3 ( )

Manual de usuario Cal Spas, modelo LTR20101000

Fabricar: Cal Spas
Tamaño del archivo: 6.73 mb
Nombre del archivo: 2010_03_01_Portable_Spa_Owner_Manual_US_after3_1_10.pdf
Idioma del manual:en
Enlace gratuito para este manual disponible en la parte inferior de la página



Resumen del manual


Do not use extension cords! Always use a weatherproof-covered receptacle. Receptacle shall be located not less than 5 feet (1.5 m) from and not exceeding 10 feet (3.0 m) from the inside wall of the spa. (NEC 680.43(A)) Do not bury the power cord. If your cord becomes damaged, replace it before next usage. All 120V spas must have a GFCI. This can be either a 20 amp GFCI receptacle or a 20 amp GFCI cord and plug kit as shown (CKIT110 - P/N ELE09700086). Test the GFCI plug prior to first use and periodically when the spa is powered. To test the GFCI plug version, follow these instructions. (Spa should already be plugged in and operational.) Press the TEST button on the GFCI. The GFCI will 1. trip and the spa will stop operating. Press the RESET button on the GFCI. The GFCI 2. will reset and the spa will turn back on. The spa is now safe to use. If the GFCI trips while the spa is in use, press the RESET button. If the GFCI does not reset, unplug the spa and call your local Cal Spas dealer for service. DO NOT USE THE SPA! 240 Volt Electrical Installation All 240V spas must be permanently connected (hardwired) to the power supply. See the wiring diagram on page 7. These instructions describe the only acceptable electrical wiring procedure. Spas wired in any other way will void your warranty and may result in serious injury. When installed in the United States, the electrical wiring of this spa must meet the requirements of National Electric Code, ANSI/NFPA 70-2008 and any applicable local, state, and federal codes. The electrical circuit must be installed by an electrical contractor and approved by a local building or electrical inspector. Failure to comply with state and local codes may result in fire or personal injury and will be the sole responsibility of the spa owner. GFCI and Wiring Requirements The power supplied to the spa must be on a dedicated GFCI protected circuit as required by ANSI/NFPA 70 with no other appliances or lights sharing the power. Use copper wire with THHN insulation. Do not use aluminum wire. Use the table on the next page to determine your GFCI and wiring requirements. When NEC requires the use of wires larger than #6 AWG, install a junction box near the spa and use #6 AWG wire between the junction box and the spa. Wire runs over 85 feet must increase wire gauge to the next lower number. For example: A normal 50 amp GFCI with four #8 AWG Copper wires run over 85 feet would require you to go to four #6 AWG copper wires. Read and follow the heater manufacturer’s safety and installation instructions prior to installation and operation. Incorrect installation may damage the heater and void its warranty. Testing the GFCI Breaker Test the GFCI breaker prior to first use and periodically when the spa is powered. To test the GFCI breaker follow these instructions (spa should be operating): Press the TEST button on the GFCI. The GFCI will 1. trip and the spa will shut off. Reset the GFCI breaker by switching the breaker 2. to the full OFF position, wait a moment, then turn the breaker back on. The spa should have power again. 240V GFCI and Wiring Requirements All 5100 and 6200 control systems are set at the factory to run on the low power setting for 40 amp operation. This is the default setting. Spa owners can have their installer change this setting so the spa will run on high power for 50 amp operation. Warning: Never set a spa to run on high power without installing a properly rated GFCI. Spa Model GFCI Required Wires Required 4050 control box (5100 and 6200 systems) Power saver mode -- this is the factory default setting One 40 amp GFCI Four #8 AWG copper wires 4050 control box (5100 and 6200 systems) High power setting -- See configuration instructions below. One 50 amp GFCI Four #8 AWG copper wires 9800 control box (except Ultimate Fitness spas -- see below) One 50 amp GFCI Four #8 AWG copper wires 5060 control box (6300 system) Default high power setting -- See configuration instructions on page 6. One 60 amp GFCI Four #8 AWG copper wires Ultimate Fitness Spas: Fitness spa with 5.5 kW heater: F854, F1257, FP2400 One 50 amp GFCI Four #8 AWG copper wires Fitness spa with 11 kW heater: F1257, F1455, FP1655, FP2500, FP2400 SEE PAGES 6 AND 7 FOR INSTALLATION DIAGRAM. Service 1: One 60 amp GFCI Service 1: Four #8 AWG copper wires Service 2: One 30 amp GFCI Service 2: Three #8 AWG copper wires Fitness Pro 4700 spa SEE PAGES 6 AND 7 FOR INSTALLATION DIAGRAM. Service 1 (swim side): One 60 amp GFCI Service 1: Four #8 AWG copper wires Service 2 (swim side): One 30 amp GFCI Service 2: Three #8 AWG copper wires Service 3 (spa side): One 40 amp GFCI Service 3: Four #8 AWG copper wires 4050 System High Power Configuration Applies to 5100 and 6200 systems To operate the spa in high power mode, ensure the following steps are performed before starting your spa: When installing the electrical system, use a 50 amp • GFCI. Follow the GFCI wiring diagram on the next page. Have your dealer or installer set d...


Comentarios



Tu reseña
Tu nombre:
Introduzca dos números de la imagen:
capcha





Categoría