Iniciar sesión:
Votos - 3, Puntuación media: 4.7 ( )

Manual de usuario Bradford-White Corp, modelo HW-670

Fabricar: Bradford-White Corp
Tamaño del archivo: 1.23 mb
Nombre del archivo:
Idioma del manual:en
Enlace gratuito para este manual disponible en la parte inferior de la página



Resumen del manual


This is not a warranty failure. An expansion tank or a similar device may be required in the inlet supply line between the appliance and the meter or valve to compensate for the thermal expansion of water under supply pressure, see figure 1. An air separator as shown in the piping diagrams is recommended especially for modern commercial hydronic systems. 5. VENT VALVES It is recommended that automatic, loose key or screwdriver type vent valves be installed at each convector or radiator. 6. MANIFOLD HEADERS Split systems with individual supply and return lines from the boiler room should normally have this piping connected to supply and return manifold headers near the boiler. To achieve good water distribution with maximum pressure drop for several circuits, manifolds of at least 2-1/2" (64mm) diameter are suggested on HWB/HW-399, HWB/HW-420, HWB/HW-520, HWB/HW-610 and HW-670 units. HWB/HW-300 units should have 1-1/2" (38mm) diameter manifolds. The circuits should be spaced on the header at a minimum of 3" (76mm) center to center. Install a balancing cock in each return line. Manifold headers are recommended for split systems with or without zone valves and also those installations with zone circulators. If the system is to be split at remote points, good practice requires special attention be given to main pipe sizing to allow balancing of water flow. The boiler piping system of a hot water boiler connected to heating coils located in air handling units where they may be exposed to refrigerated air circulation must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. 7. COOLING PIPING When the boiler is used in conjunction with a refrigeration system it must be installed so that the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler, fig. 4. Water temperature in the heating system must be reduced to less than 1000F (38°C) before cooling system is started, or damage to the chiller unit may occur. SCHEMATIC SHOWING PROPER PIPING ISOLATION OF THE BOILER FROM THE CHILLER FIGURE 4 If the boiler is connected to chilled water piping or its heating coils are exposed to refrigerated air, the boiler piping system must be equipped with flow valves or other automatic means to prevent gravity circulation through the boiler during the cooling cycle. 8. CIRCULATING PUMP CONSTANT CIRCULATING PUMP OPERATION OF THE BOILER VOIDS THE WARRANTY. Constant water flow through the unit will “wash” away the copper’s natural protective coating. This is called velocity erosion. This erosion is not as great a problem when intermittent circulating operation is used per the recommended installation procedure. Constant circulation of water through the building’s system main is permissible as long as the water does not constantly flow through the boiler. Only all bronze or stainless steel circulators are to be used with the unit when it is installed in HOT WATER SUPPLY SYSTEMS. A TYPICAL CIRCULATING PUMP FIGURE 5 Although each circulator that requires oiling is oiled and operated by the manufacturer, IT MUST BE OILED AGAIN BEFORE OPERATED. Oil the three oil cups (2 on the motor, 1 on the pump) as instructed on the oil tube supplied with the unit, fig 5. Thereafter, during the heating season, lubricate the three oil cups at least once every four months. Combination heating-cooling systems should be lubricated every four months year ‘round. Use 2 or 3 teaspoonsful in bearing oil cups, fig. 5, and 10 or 12 drops in the motor oil cups. Use No. 20 non-detergent motor oil. Follow the same oiling procedure if a replacement circulator is installed into the system. GAS CONNECTIONS WARNING THIS BOILER IS NOT INTENDED TO OPERATE AT GAS SUPPLY PRESSURE OTHER THAN SHOWN ON THE RATING PLATE. EXPOSURE TO HIGHER GAS SUPPLY PRESSURE MAY CAUSE DAMAGE TO GAS VALVES WHICH CAN RESULT IN FIRE OR EXPLOSION. IF OVERPRESSURE HAS OCCURRED SUCH AS THROUGH IMPROPER TESTING OF GAS LINES OR EMERGENCY MALFUNCTION OF THE SUPPLY SYSTEM, THE GAS VALVES MUST BE CHECKED FOR SAFE OPERATION. MAKE SURE THAT THE OUTSIDE VENTS ON THE SUPPLY REGULATORS AND THE SAFETY VENT VALVESARE PROTECTED AGAINST BLOCKAGE. THESE ARE PARTS OF THE GAS SUPPLY SYSTEM, NOT THE BOILER. VENT BLOCKAGE MAY OCCUR DURING ICE BUILD-UP OR SNOW STORMS. WHEN LOCAL CODES REQUIRE A MAIN MANUAL SHUTOFF VALVE OUTSIDE THE BOILER JACKET,ASUITABLE MAIN MANUAL SHUTOFF VALVE MUST BE INSTALLED IN A LOCATION COMPLYING WITH THOSE CODES. 9 99999 IT IS IMPORTANTTO GUARDAGAINST GAS VALVE FOULING FROM CONTAMINANTS IN THE GAS WAYS. SUCH FOULING MAY CAUSE IMPROPER OPERATION, FIRE OR EXPLOSION. IF COPPER SUPPLY LINES ARE USED THEY MUST BE CERTIFIED FOR GAS SERVICE. BEFORE ATTACHING THE GAS LINE BE SURE THAT ALL GAS PIPE IS CLEAN ON THE INSIDE. TO TRAPANY DIRT OR FOREIGN MATERIAL IN THE GAS SUPPLY LINE, A DIRT LEG (SOMETIMES CALLED DRIP LEG or sediment trap) MUST BE...

Otros modelos de este manual:
Calentadores de Agua - HW-399 (1.23 mb)
Calentadores de Agua - HW-520 (1.23 mb)
Calentadores de Agua - HWB-300 (1.23 mb)
Calentadores de Agua - HWB-399 (1.23 mb)

Comentarios



Tu reseña
Tu nombre:
Introduzca dos números de la imagen:
capcha





Categoría