|
Resumen del manual
_______________Btu/Hr (maximum the space can support) _______________Btu/Hr (actual amount of Btu/Hr used) Example: 51,200 Btu/Hr (maximum the space can support) 70,000 Btu/Hr (actual amount of Btu/Hr used) The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows: A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 7. B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7. C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined. If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation. WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air byoneofthemethodsdescribed in the National Fuel Gas Code, ANSIZ223.1/NFPA54Section5.3 or applicable local codes. 114683-01B AIR FOR COMBUSTION AND VENTILATION Continued VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts. Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12” of the ceiling and one within 12” of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts. IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat- controlled power vent. Heated air entering the attic will activate the power vent. Figure 2 - Ventilation Air from Inside Building Or Remove Door into Adjoining Room, Option 3 Ventilation Grills Into Adjoining Room, Option 2 12" 12" Ventilation Grills into Adjoining Room, Option 1 Figure 3 - Ventilation Air from Outdoors Outlet Air Ventilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic INSTALLATION NOTICE: This heater is intended for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri- mary heat source. If you have a central heatingsystem, you may run system’s circulating blower while using heater. This will help circulatetheheatthroughoutthe house. In the event of a power outage, you can use this heater as your primary heat source. WARNING: A qualified ser- vice person must install heater. Follow all local codes. CHECK GAS TYPE Use only the correct type of gas (natural or pro- pane/LP). If your gas supply is not the correct gas type, do not install heater. Call dealer where you bought heater for proper type heater. WARNING: This appliance is equipped for (natural or pro- pane/LP) gas. Field conversion is not permitted. 114683-01B INSTALLATION Continued INSTALLATION ITEMS Before installing heater, make sure you have the items listed below. • forpropane/LPgas,externalregulator(supplied by installer) • piping (check local codes) • sealant (resistant to propane/LP gas) • equipment shutoff valve * • ground joint union • sediment trap • tee joint • pipe wrench • for natural gas, test gauge connection* * ACSAdesign-certifiedequipmentshutoffvalve with 1/8" NPT tap is an acceptable alternative to test gauge connection. The optional CSA design- certified equipment shutoff valve can be purchased from your dealer. See Accessories, page 30. LOCATING HEATER This heater is designed to be mounted on a wall. WARNING: Maintain the minimum clearances shown in Figure 4. If you can, provide greater clearances from floor, ceiling and joining wall. You can locate heater on floor, away from a wall. An optional floor mounting stand is needed. Purchase the floor mounting stand from your dealer. See Accessories, page 30. WARNING: Never install the heater • in a bedroom or bathroom • in a recreational vehicle • where curtains, furniture, clothing or other flammable objectsarelessthan36inches from the front, top or sides of the heater • as a fireplace insert ...
Otros modelos de este manual:Los calentadores de gas - BG30N (1.15 mb)
Los calentadores de gas - BG30P (1.15 mb)
Los calentadores de gas - BG30PT (1.15 mb)
Los calentadores de gas - FG30N (1.15 mb)