• Use 4” pipe if you have more than 15 feet of equivalent vent length. • Horizontal runs shall not exceed 10 feet of EVL. • It is recommended that vertical runs be a minimum of 8 feet. • To calculate EVL, use the following conversions: 90. elbow or “T” = 5 equivalent feet 45. elbow = 3 equivalent feet Horizontal Pipe Run = 1 equivalent foot per actual foot Vertical Pipe Run = 0.5 equivalent foot per actual foot NOTE: At altitudes above 3,000 feet, we suggest the use of 4” diameter vent at an EVL
You should adjust the damper based on the fire’s appearance. A low, reddish, dirty fire can be improved by pulling the damper out slightly. A “blow torch” fire can be improved by pushing the damper in a bit. As a general rule, on lower feed rate settings, the damper should be in farther. On higher feed rates, the damper should be more open. Through trial and error, you will find the best setting. Consult your dealer if you need help. NOTE: On “1”, damper should be out approximately 1/8” to .”. I
Ashes must be disposed in a metal container with a tight lid and placed on a no combustible surface well away from the home structure. · This stove must be connected to a standard 120 V., 60 Hz grounded electrical outlet. Do not use an adapter plug or sever the grounding plug. Do not route the electrical cord underneath, in front of, or over the stove. · The exhaust system should be checked, at a minimum, at least twice a year for any build up of soot or creosote. · Keep foreign objects out of t