Please Note: A major cause of chimney related fires is due to a failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance that this fireplace and vent system be installed only in accordance with these instructions. Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher. Clearances to Combustibles Dimension Description E33 A* From Unit to Side Walls 8” (203mm) B From Unit to Ceiling 47” (1194mm) C Minimum Mantel Height 15” (381mm) D Maximum Mantel Depth 12” (305mm) E Alcove Width 76” (1930mm) F Alcove Depth 36” (914mm) G Hearth Height 1-%” (32mm) H Hearth Width 45-/” (1156mm) I Hearth Depth 13” (330mm) 12 10 8 6 * Alcove side wall must have a minimum of 8” (203mm) clearance on one side. 20 - 18 -16 - 47” I4-(1194mm) to ceiling 10 -8 6 4 -2 0- t 12" (305mm) Mantel 3-1/2" (89mm) Mantel 20” i[508mm) 15” f-(381mm) 25" (635mm) to floor Top Of Unit Side View Flush Front Mantel Clearances Mantle Faceplate Hearth 12" Max. D I ^ i Combustible _ ! Flooring Existing Hearth ■4-¡-► I 16" Min. Flush with Floor Note: A non-combustible mantel may be installed at a lower height. Note: Ensure the paint that is used on the mantel and the facing is “heat resistant” or the paint may discolour. 128 June 2007 Regency Product Specifications Book...