When you receive the shipment, inspect the container and equipment for signs of damage. Note any evidence of rough handling in transit. Immediately report any damage to the shipping agent. The carrier will not honor damage claims unless all shipping material is saved for inspection. After examining and removing contents, save packing material and carton in the event reshipment is necessary. TABLE OF CONTENTS Chapter 1 Introduction ......................................... 1 1.1 General Descripti
It is recommended that you put the controller in the Standby Mode for any configuration change other than Setpoints & Alarms. Figure 3.9 Flow Chart for Output 1 36 ENTER OUTPUT 1 MENU: Press a 1) Press a, if necessary, until CNFG prompt appears. Press d 2) Display advances to INPT Input Menu. Press a 3) Press a, if necessary, until Display advances to OUT1 Output 1 Menu. Press d 4) Display advances to SELF Self Submenu. SELF SUBMENU: The Self Option allows the output of the instrument to be cont
Decimal Point for Process Input Type is passive. TEMPERATURE UNIT SUBMENU: Press d 8) Display flashes previous Temperature Unit selection. Press b 9) Scroll though the available selections to the Temperature Unit of your choice: °F or °C. Press d 10) Display shows STRD stored message momentarily and then advances to FLTR Filter Constant. FILTER CONSTANT SUBMENU: Press d 11) Display flashes previous selection for Filter Constant. Press b 12) Scroll though the available selections: 0001, 0002, 000
Box 4047 ISO 9001 Certified Stamford CT 06907-0047 TEL: (203) 359-1660 FAX: (203) 359-7700 e-mail: info@omega.com Canada: 976 Bergar Laval (Quebec) H7L 5A1 TEL: (514) 856-6928 FAX: (514) 856-6886 e-mail: info@omega.ca For immediate technical or application assistance: USA and Canada: Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA® Customer Service: 1-800-622-2378 / 1-800-622-BEST® Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN® Mexico and TEL: (001) 203-359-7803 FAX: (001) 203-359-7807 Lat
Do not attempt to change these parameters. LINE FEED SUBMENU: Determines if data sent from the instrument will have a Line Feed appended to the end - useful for viewing or logging results on separate lines when displayed on communications software at a computer. Press d 22) Display flashes previous selection for “Line Feed”. Press b 23) Scroll through the available selections: NO, YES. Press d 24) Display shows STRD stored message momentarily and then advances to ECHO only, if it was changed, ot
Press d 2) Display advances to INPT Input Menu. Press d 3) Display flashes T.c, RTD or PROC (Thermocouple, RTD or Process). If the displayed input type is T.c, press a to skip to step 6 (T.c stops flashing). THERMOCOUPLE SUBMENU: Press b 4) Scroll through the available selection to T.c (flashing). Press d 5) Display shows STRD stored message momentarily and then T.c (not flashing). Press d 6) Display flashes previous thermocouple type selection. i.e. J (see below for types). Press b 7) Scroll th
During Standby Mode, the instrument remains in a ready condition, but all outputs are disabled. Standby Mode is useful when maintenence of the system is necessary. When the instrument is in "RUN" Mode, push d twice to disable all outputs and alarms. It is now in "STANDBY" Mode. Push d once more to resume "RUN" Mode. PUSH d TWICE to disable the system during an EMERGENCY. To Reset the Meter: When the controller is in the "MENU" Mode, push c once to direct controller one step backward of the top m
When a numerical value is displayed press this key to increase value of a parameter that is currently being modified. • Holding the b button down for approximately 3 seconds will speed up the rate at which the set point value increments. • In the Run Mode press b causes the display to flash the PEAK value – press again to return to the Run Mode. c (DOWN) • Press the down c button to go back to a previous Top Level Menu item. • Press this button twice to reset the controller to the Run Mode. • Wh
max NETWORK AND COMMUNICATIONS (Optional -C24, -C4EI, -EI) Ethernet: Standards Compliance IEEE 802.3 10Base-T Supported Protocols: TCP/IP, ARP, HTTPGET RS-232/RS-422/RS-485/MODBUS: Selectable from menu; both ASCII and modbus protocol selectable from menu. Programmable 300 to 19.2 K baud; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status. RS-485 Addressable from 0 to 199 Connection Screw terminals ALARM 1 & 2
CAUTION or WARNING: Tells you about the risk of electrical shock. CAUTION, WARNING or IMPORTANT: Tells you of circumstances or practices that can effect the instrument’s functionality and must refer to accompanying documents. TIP: Provides you helpful hints. 1 PART 1 INTRODUCTION 1.1 Description This device can be purchased as monitor (read process value only) or as a controller. • The iSeries controller offers unparalleled flexibility in process measurement. Each unit allows the user to select