Iniciar sesión:
Votos - 2, Puntuación media: 4 ( )

Manual de usuario Heat & Glo LifeStyle, modelo ST-HV-IPI

Fabricar: Heat & Glo LifeStyle
Tamaño del archivo: 3.11 mb
Nombre del archivo:
Idioma del manual:en
Enlace gratuito para este manual disponible en la parte inferior de la página



Resumen del manual


FLAME SENSOR ROD NAILING TABS (BOTH SIDES) 36 Heat & Glo • PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI • 2005-900 Rev. K • 11/06 • Insert insulation from the outside of the fireplace and pack the insulation tightly to totally seal between the pipe and the outer casing. • At the gas line access hole the gap between the supply piping and gas access hole can be plugged with noncombustible insulation to prevent cold air infiltration. Step 6. The Gas Supply Line NOTE: Have the gas supply line installed in accordance with local building codes by a qualified installer approved and/or licensed as required by the locality. (In the state of Massachusetts installation must be performed by a licensed plumber or gas fitter). NOTE: Before the first firing of the fireplace, the gas supply line should be purged of any trapped air. NOTE: Consult local building codes to properly size the gas supply line leading to the 1/2 inch (13 mm) hook-up at the unit. This gas fireplace is designed to accept a 1/2 inch (13 mm) gas supply line. To install the gas supply line: • A listed (and State of Massachusetts approved) 1/2 inch (13mm) tee-handle manual shut-off valve and a listed flexible gas connector are connected to the 1/2 inch (13mm) inlet of the control valve. NOTE: If substituting for these components, please consult local codes for compliance. • Locate the gas line access hole in the outer casing of the fireplace. • The gas line may be run from either side of the fireplace provided the hole in the outer wrap does not exceed 2” in diameter and it does not penetrate the actual firebox. • Open the fireplace lower grille, insert the gas supply line through the gas line hole, and connect it to the shut-off valve. • When attaching the pipe, support the control so that the lines are not bent or torn. • After the gas line installation is complete, all connections must be tightened and checked for leaks with a commercially-available, non-corrosive leak check solution. Be sure to rinse off all leak check solution following testing. WARNING: DO NOT USE AN OPEN FLAME ! TO CHECK FOR GAS LEAKS. Step 7. Gas Pressure Requirements Pressure requirements for Heat & Glo gas fireplaces are shown in the table below. Pressure Natural Gas Propane Minimum 5.0 inches 11.0 inches Inlet Pressure w.c. w.c. Maximum Inlet 14.0 inches 14.0 inches Gas Pressure w.c. w.c. Manifold 3.5 inches 10.0 inches Pressure w.c. w.c. A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is provided on the inlet and outlet side of the gas control for a test gauge connection to measure the manifold pressure. The fireplace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing of the system at test pressures in excess of one-half (1/2) psig (3.5 kPa). The fireplace must be isolated from the gas supply piping system by closing its individual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than one-half (1/2) psig (3.5 kPa). Figure 33. Gas Supply Line USE A WRENCH ON SHUT-OFF VALVE WHEN TIGHTENING GAS LINE. MANUAL SHUT-OFF VALVE FLEX CONNECTOR GAS VALVE GAS LINE ACCESS CONTROL VALVE Heat & Glo • PIER-HV-IPI, ST-HV-IPI, L&R-COR-HV-IPI • 2005-900 Rev. K • 11/06 37 Step 8. Wiring the Fireplace NOTE: Electrical wiring must be installed by a licensed electrician. CAUTION: DISCONNECT REMOTE CONTROLS IF ABSENT FOR EXTENDED TIME PERIODS. THIS WILL PREVENT ACCIDENTAL FIREPLACE OPERATION. For Intermittent Pilot Ignition Wiring Appliance Requirements This appliance requires that 110-120 VAC be wired to the junction box. Maintain correct polarity when wiring the junction box. Figure 34. Intermittent Pilot Ignition (IPI) Wiring Diagram Operation using Battery Power This fireplace has an optional battery operation. The system is fully functional with the use of two “D” size batteries without ordinary 110-120 VAC power. Wiring to the battery pack should be left disconnected in order to conserve battery life. In the case of a loss of power, simply connect red and black wire leads to activate battery power (connect red to red, black to black). The fireplace can be used as necessary. Once power (110 VAC) is restored, disconnect red and black wire leads to extend battery life. WARNING Wire 110V to electrical junction box. Do NOT wire 110V to valve. Do NOT wire 110V to wall switch. • Incorrect wiring will damage millivolt valves. • Uninterrupted or continuous power is required at all times in IPI system EXCEPT when using battery back-up. • Incorrect wiring will override IPI safety lockout and may cause explosion. IGNITION MODULE (3V) VALVE LOW VOLTAGE PLUG-IN 3V TRANSFORMER NEUTRAL HOT GROUND FLAME SPARKER/ SENSOR REMOTE CONTROL SEE NOTE 1 IGNITION MODULE 3 VAC INTERMITTENT PILOT IGNITOR GROUND TO FIREPLACE CHASSIS VALVE TRANSFORMER 3 VAC ORG WHT ORG GRN WHT ON/OFF WALL SWITCH BRN BRN BLK WHT BLK WHT BLK WHT BLK TERMINAL BLOCK BULB SOCKET ASSEMBLY (3) FLAME ON/OFF PLUG IN BLACK W...

Otros modelos de este manual:
chimeneas - LCOR-HV-IPI (3.11 mb)
chimeneas - PIER-HV-IPI (3.11 mb)
chimeneas - RCOR-HV-IPI (3.11 mb)

Comentarios



Tu reseña
Tu nombre:
Introduzca dos números de la imagen:
capcha





Categoría